Configure Counters - Woodward easYgen-2000 Series User Manual

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

4.8

Configure Counters

General notes
ID
Parameter
2550
Maintenance
hours
2562
Reset mainte‐
nance period
hrs
2551
Maintenance
days
2563
Reset mainte‐
nance period
days
2567
Code level for
reset maint.
37535B
CL
Setting range
Description
[Default]
2
0 to 9,999 h
This parameter defines the remaining hours until the next maintenance call
occurs. Once the generator has been operated for the number of hours con‐
[300 h]
figured here, a maintenance message is displayed.
If the maintenance counter is reset either by the push-buttons at the front
panel (refer to
the parameter "Reset maintenance call" to "Yes" (parameter
the maintenance counter is reset to the configured value.
Notes
To disable the "maintenance hours" counter configure "0" for this entry.
2
Yes / No
If this parameter is configured to "Yes" the maintenance "hours" counter is
reset to the configured value. Once the counter "maintenance hours" has
[No]
been reset, the control unit changes this parameter to "No".
Notes
When using a specific code level in parameter
tenance hours this parameter can be blocked.
2
0 to 999 d
This parameter defines the remaining days until the next maintenance call
occurs. Once the configured number of days has expired since the last main‐
[365 d]
tenance, a maintenance message is displayed.
If the maintenance counter is reset either by the push-buttons at the front
panel (refer to
the parameter "Reset maintenance call" to "Yes" (parameter
the maintenance counter is reset to the configured value.
Notes
To disable the "maintenance days" counter configure "0" for this entry.
2
Yes / No
If this parameter is configured to "Yes" the "maintenance days" counter is
reset to the configured value. Once the counter has been reset, the control
[No]
unit changes this parameter to "No".
Notes
When using a specific code level in parameter
tenance days this parameter can be blocked.
2
This parameter determines the required code level for resetting the counter
"Maintenance call in...". User with a lower code level may not access this
function.
The following code levels exist:
0
Operator
easYgen-2200/2500 | Genset Control
Maintenance call
A maintenance call will be issued if the configured
number of maintenance hours has expired or the con‐
figured number of days has expired since the last
maintenance.
In case of a maintenance call, the display indicates
"Mainten. days exceeded" or "Mainten. hours
exceeded".
Ä Chapter 5.2.1 "Front Panel" on page 340 ), or by configuring
Ä Chapter 5.2.1 "Front Panel" on page 340 ), or by configuring
Configuration
Configure Counters
2562 Ä p.
327),
2567 Ä p. 327
to reset main‐
2563 Ä p.
327),
2567 Ä p. 327
to reset main‐
327