Breakers Gcb - Woodward easYgen-2000 Series User Manual

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

ID
Parameter
12931
Transition
mode 1
3400
Transfer time
GCB↔MCB
5820
Dead bus
detection max.
volt.
4.5.1.8

Breakers GCB

General notes
Fig. 83: Normally Open contacts -
37535B
Configure Application > Configure Breakers > Breakers GCB
CL
Setting range
Description
[Default]
Notes
This parameter only applies to application mode
For a detailed explanation for each mode refer to
tion Modes (Breaker Logic)" on page 195 .
2
Determined by
Once the conditions of the LogicsManager have been fulfilled, the transition
LogicsManager
mode configured in parameter
standard transition mode configured in parameter
[(0 & 1) & 1]
For information on the LogicsManager and its default settings see
Ä Chapter 9.4.1 "LogicsManager Overview" on page 549 .
Notes
This parameter only applies to application mode
2
0.10 to 99.99 s
Switching from generator supply to mains supply or from mains supply to gen‐
erator supply occurs automatically if the operating conditions have been met.
[1.00 s]
The time between the reply "power circuit breaker is open" and a close pulse
is set by this parameter. This time applies for both directions. During this time
the consumers are de-energized.
Notes
This parameter only applies to application mode
This is only valid, if parameter
TION
2
0 to 30 %
If the busbar voltage falls below this percentage of the busbar 1 rated voltage
(parameter
[10 %]
command variable 02.21 (Busbar 1 is dead) becomes TRUE.
schematic
easYgen-2200/2500 | Genset Control
3412 Ä p. 200
3411 Ä p. 200
1781 Ä p.
95), a dead bus condition is detected and the logical
Normally Open (N.O.) contacts
The relay (discrete output) must be energized to close
the contact.
Configuration
.
Ä Chapter 4.5.1.6 "Transi‐
will be used instead of the
3411 Ä p.
200.
.
.
is configured to OPEN TRANSI‐
201