ID
Parameter
15106
J1939 own
address
15107
Engine control
address
37535B
CL
Setting range
Description
[Default]
MFR/EDC7
The MAN MFR/EDC7 ECU is enabled: J1939 data according to the
MAN
SAE J1939 standard and some EDC-specific data are considered.
EEM SISU
The SISU EEM2/3 ECU is enabled: J1939 data according to the SAE J1939
standard and some EEM2/3-specific data are considered.
Cummins
The Cummins ECU is enabled: J1939 data according to the SAE J1939
standard and some Cummins-specific data are considered.
This setting is also recommended for Cummins CM570 and CM850.
ADEC ECU8
The MTU ADEC ECU8 with SmartConnect is enabled: J1939 data according
MTU
to the SAE J1939 standard and some ADEC-specific data are considered.
2
0 to 255
The easYgen sends J1939 request and control messages with this source
address. It must be changed for different ECU types according to the fol‐
[234]
lowing table. The ECU listens only to control messages, if they are sent to the
correct address.
n
n
n
n
n
n
n
n
n
n
Details may be found in the manual of the genset control and in
Ä Chapter 7.5 " J1939 Protocol" on page 456 .
Notes
Changing this parameter becomes only effective after restarting the unit.
2
0 to 255
Configures the address of the J1939 device, which is controlled. The
easYgen sends J1939 request and control messages with this destination
[0]
address.
n
n
n
n
n
n
n
n
n
n
Details may be found in the manual of the genset control and in
Ä Chapter 7.5 " J1939 Protocol" on page 456 .
easYgen-2200/2500 | Genset Control
Configure Interfaces > CAN Interface 2 > J1939 Interface
S6 Scania: 39
EMR2 Deutz: 3
EMS2 Volvo: 17
ADEC ECU7 MTU: 1
EGS Woodward: 234
MFR/EDC7 MAN: 253
EEM SISU: N/A
Cummins: 220
ADEC ECU8 MTU: 234
Ä Chapter 7.5 " J1939 Protocol" on page 456
Standard: Please refer to
and to the manual of your J1939 ECU manufacturer.
S6 Scania: 0
EMR2 Deutz: 0
EMS2 Volvo: 0
ADEC ECU7 MTU: 128
EGS Woodward: 0
MFR/EDC7 MAN: 39
EEM SISU: 0/(1)
Cummins: 0
ADEC ECU8 MTU: 0
Ä Chapter 7.5 " J1939 Protocol" on page 456
Standard: Please refer to
and to the manual of your J1939 ECU manufacturer.