Woodward easYgen-2000 Series User Manual page 95

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

ID
Parameter
1601
Engine rated
speed
1766
Generator
rated voltage
1768
Mains rated
voltage
1781
Busbar 1 rated
voltage
1752
Gen. rated
active power
[kW]
1758
Gen. rated
react. power
[kvar]
1754
Generator
rated current
1748
Mains rated
active power
[kW]
1746
Mains rated
react. pwr.
[kvar]
1785
Mains rated
current
1858
1Ph2W voltage
measuring
37535B
CL
Setting range
Description
[Default]
2
500 to 4,000
Number of revolutions per minute of the engine at rated engine speed. The
rpm
speed control with an ECU via J1939 CAN bus refers to this value.
[1,500 rpm]
2
50 to 650000 V
This value refers to the rated voltage of the generator (generator voltage on
data plate) and is the voltage measured on the potential transformer primary.
[400 V]
The generator rated voltage is used as a reference figure for all generator
voltage related functions, which use a percentage value, like generator
voltage monitoring, breaker operation windows or the Analog Manager.
2
50 to 650000 V
This value refers to the rated voltage of the mains and is the voltage meas‐
ured on the potential transformer primary.
[400 V]
The mains potential transformer primary voltage is entered in this parameter.
The mains rated voltage is used as a reference figure for all mains voltage
related functions, which use a percentage value, like mains voltage moni‐
toring, breaker operation windows or the Analog Manager.
2
50 to 650000 V
This value refers to the rated voltage of busbar 1 and is the voltage measured
on the potential transformer primary.
[400 V]
If voltage measuring is configured to 1Ph 3W, the WYE voltage (VL1N) must
be entered here.
The busbar 1 potential transformer primary voltage is entered in this param‐
eter. The busbar rated voltage is used as a reference figure for all busbar
voltage related functions, which use a percentage value, like synchronization.
2
0.5 to 99999.9
This value specifies the generator real power rating, which is used as a refer‐
kW
ence figure for related functions. The generator rated active power is the gen‐
erator apparent power multiplied by the generator power factor (typically
[200.0 kW]
~0.8). These values are indicated in the generator data plate (
cies" on page 94 ).
2
0.5 to 99999.9
This value specifies the generator reactive power rating, which is used as a
kvar
reference figure for related functions. The generator rated reactive power also
depends on the generator values (
[200.0 kvar]
2
1 to 32000 A
This value specifies the generator rated current, which is used as a reference
figure for related functions.
[300 A]
2
0.5 to 99999.9
This value specifies the mains real power rating, which is used as a reference
kW
figure for related functions. The mains rated active power is a reference value
used by several monitoring and control functions (
[200.0 kW]
on page 94 ).
2
0.5 to 99999.9
This value specifies the mains reactive power rating, which is used as a refer‐
kvar
ence figure for related functions.
[200.0 kvar]
The mains rated reactive power is a reference value used by several moni‐
toring and control functions(
2
5 to 32000 A
This value specifies the mains rated current, which is used as a reference
figure for related functions.
[300 A]
3
[Phase -
The unit is configured for measuring phase-phase voltages if 1Ph 2W meas‐
phase]
uring is selected.
Phase - neutral
The unit is configured for measuring phase-neutral voltages if 1Ph 2W meas‐
uring is selected.
easYgen-2200/2500 | Genset Control
Configure Measurement
Ä "Dependencies" on page 94 ).
Ä "Dependencies"
Ä "Dependencies" on page 94 ).
Configuration
Ä "Dependen‐
95