Application
Modbus Applications > Changing Parameter Settings > Parameter Setting
Example 1: Addressing the pass‐
word for serial interface 1
Example
Example 2: Addressing the gener‐
ator rated voltage
Example
434
The new entered value must comply with the param‐
eter setting range when changing the parameter set‐
ting.
ID
Parameter
10401
Password for serial interface1
Modbus address = 400000 + (Par. ID + 1) = 410402
n
Modbus length = 1 (UNSIGNED 16)
n
Fig. 217: Modscan32 at address 410402
Set the configuration to address parameter 10401 as shown
in (Fig. 217).
ID
Parameter
1766
Generator rated voltage
Modbus address = 40000 + (Par. ID + 1) = 41767
n
Modbus length = 2 (UNSIGNED 32)
n
Fig. 218: Modscan32 at address 41767
Set the configuration to address parameter 1766 as shown in
(Fig. 218).
easYgen-2200/2500 | Genset Control
Setting range
Data type
0000 to 9999
UNSIGNED 16
Setting range
Data type
50 to 650000 V
UNSIGNED 32
37535B