Woodward easYgen-2000 Series User Manual page 126

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

Configuration
Configure Monitoring > Generator > Generator Ground Fault (Le...
ID
Parameter
3251
Alarm class
3257
3252
Self acknowl‐
edge
3258
3253
Delayed by
engine speed
3259
126
CL
Setting range
Description
[Default]
Notes
If the monitored ground fault falls below the threshold (minus the hysteresis)
before the delay expires the time will be reset.
2
Class A/B/C/D/
Each limit may be assigned an independent alarm class that specifies what
E/F
action should be taken when the limit is surpassed.
3251: [B]
3257: [F]
Notes
For additional information refer to
on page 587
2
Yes
The control unit automatically clears the alarm if the fault condition is no
longer detected.
[No]
The control unit does not automatically reset the alarm when the fault condi‐
tion is no longer detected.
The alarm must be acknowledged and reset by manually pressing the appro‐
priate buttons or by activating the LogicsManager output "External acknowl‐
edgement" (via a discrete input or via an interface).
2
Yes
Monitoring for fault conditions is not performed until engine delayed moni‐
toring is enabled. The engine monitoring delay time (param‐
eter
parameters assigned this delay.
[No]
Monitoring for this fault condition is continuously enabled regardless of engine
speed.
easYgen-2200/2500 | Genset Control
Ä Chapter 9.5.1 "Alarm Classes"
3315 Ä p.
239) must expire prior to fault monitoring being enabled for
37535B