External Discrete Outputs - Woodward easYgen-2000 Series User Manual

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

ID
Parameter
12580
Ready for op.
Off
(Ready for oper‐
ation OFF)
12110
Relay {x}
Parameter IDs
R 1
Parameter ID
12580
Table 49: Discrete outputs - relay parameter IDs
4.5.6

External Discrete Outputs

37535B
CL
Setting range
Description
[Default]
2
Determined by
The "Ready for operation OFF" relay is energized by default if the power
LogicsManager
supply exceeds 8 V.
Once the conditions of the LogicsManager have been fulfilled, the relay will
be de-energized. This LogicsManager output may be configured with addi‐
tional conditions, which may signal a PLC an "out of operation" condition by
de-energizing the relay on terminals 41/42, like "shutdown alarm" or no
"AUTO mode" present.
Notes
For information on the LogicsManager and its default settings see
Ä Chapter 9.4.1 "LogicsManager Overview" on page 549 .
2
Determined by
Once the conditions of the LogicsManager have been fulfilled, the relay will
LogicsManager
be energized.
Notes
For information on the LogicsManager and its default settings see
Ä Chapter 9.4.1 "LogicsManager Overview" on page 549 .
R 2
R 3
R 4
12110
12310
12320
If a Woodward IKD 1 or other external expansion board (Phoenix
Contact) is connected to the easYgen via the CAN bus, it is pos‐
sible to use 16 additional discrete outputs.
easYgen-2200/2500 | Genset Control
Configure Application > External Discrete Outputs
The parameter IDs above refers to relay 2.
Refer to Ä "Discrete outputs - relay parameter
IDs" Table on page 221 for the parameter IDs of
the parameters for relay 3 to relay 11.
R 5
R 6
R 7
12130
12140
12150
Configuration
R 8
R 9
R 10
12160
12170
12180
R 11
12560
221