LogicsManager Reference > Logical Command Variables > Group 02: Systems Condition
No.
ID
01.06
104
01.07
105
01.08
106
01.09
107
01.10
108
01.11
109
9.4.4.3

Group 02: Systems Condition

No.
ID
Name
02.01
119
Firing speed
detected
02.02
120
Speed detected
02.03
121
Generator
voltage ok
02.04
122
Generator fre‐
quency ok
02.05
123
Generator ok
02.06
124
Reserved
02.07
125
Reserved
02.08
126
Reserved
02.09
127
Mains voltage ok
02.10
128
Mains frequency
ok
02.11
129
Mains ok
562
Name / Function
Alarm class F
All alarm classes
Warning alarm
Shutdown alarm
Centralized alarm
New alarm triggered
Systems condition
n
Logic command variables 02.01-02.21
n
The status of the system may be used as command variable in a
logical output to set parameters for customized operations.
Function
Firing speed recognized (via MPU/
gen. frequency / LogicsManager)
Speed recognized (via MPU/gen.
frequency / LogicsManager)
Generator voltage within operating
window
Generator frequency within oper‐
ating window
Generator voltage and frequency
within operating windows
Mains voltage within operating
window
Mains frequency within operating
window
Mains voltage and frequency within
operating windows
easYgen-2200/2500 | Genset Control
Note
TRUE as long as an alarm of this alarm class is active or latched
(triggered)
TRUE as long as at least one alarm of the alarm classes A/B/C/D/
E/F is active or latched (triggered)
TRUE as long as at least one alarm of the alarm classes A/B is
active or latched (triggered)
TRUE as long as at least one alarm of the alarm classes C/D/E/F
is active or latched (triggered)
TRUE as long as at least one alarm of the alarm classes B/C/D/E/
F is active or latched (triggered)
TRUE if any alarm has been triggered until it is acknowledged
Note
TRUE as long as at least firing speed is measured
(defined by parameter
MPU or the generator frequency; or is detected via the
LogicsManager output "ignition speed reached" (defined
by parameters
3324 Ä p. 239
TRUE as long as a speed is measured (this can be
lower than the ignition speed; either via the MPU, the
generator frequency, or the LogicsManager output "igni‐
tion speed reached")
TRUE as long as the generator voltage is within the
operating window
TRUE as long as the generator frequency is within the
operating window
TRUE as long as the generator voltage and frequency
are within the operating windows (02.03. and 02.04 are
TRUE)
TRUE as long as the mains voltage is within the oper‐
ating window
TRUE as long as the mains frequency is within the
operating window
TRUE as long as the mains voltage and frequency are
within the operating windows (02.09. and 02.10 are
TRUE)