Engine/Generator Active Power Mismatch - Woodward easYgen-2000 Series User Manual

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

ID
Parameter
2452
Self acknowl‐
edge
4.4.3.4

Engine/Generator Active Power Mismatch

General notes
ID
Parameter
2920
Monitoring
2925
Limit
2923
Delay
2921
Alarm class
37535B
Configure Monitoring > Engine > Engine/Generator Active Po...
CL
Setting range
Description
[Default]
2
Yes
The control unit automatically clears the alarm if the fault condition is no
longer detected.
[No]
The control unit does not automatically reset the alarm when the fault condi‐
tion is no longer detected.
The alarm must be acknowledged and reset by manually pressing the appro‐
priate buttons or by activating the LogicsManager output "External acknowl‐
edgement" (via a discrete input or via an interface).
If enabled, this monitoring function becomes only active if gener‐
ator power control is enabled (refer to
Control" on page 276 ). If the measured generator power deviates
from the power setpoint by a value exceeding the limit configured
in parameter
ured in parameter
CL
Setting range
Description
[Default]
2
[On]
Monitoring of the generator active power mismatch is carried out according to
the following parameters.
Off
Monitoring is disabled.
2
0.0 to 30.0 %
If the difference between the measured generator power and the power set‐
point exceeds this value for at least the delay time (param‐
[5.0 %]
eter
class is initiated.
Notes
This value refers to the generator rated active power (parameter
1752 Ä p.
2
3 to 65000 s
If the monitored active power mismatch exceeds the threshold value config‐
ured in parameter
[30 s]
will be issued.
Notes
If the monitored active power mismatch falls below the threshold (minus the
hysteresis) before the delay expires the time will be reset.
2
Class A/B/C/D/
Each limit may be assigned an independent alarm class that specifies what
E/F
action should be taken when the limit is surpassed.
[B]
Notes
For additional information refer to
on page 587
easYgen-2200/2500 | Genset Control
2925 Ä p. 161
for a time exceeding the delay config‐
2923 Ä p.
161, an alarm will be issued.
If this protective function is triggered, the display indi‐
cates "Gen act.pwr mismatch" and the logical com‐
mand variable "06.29" will be enabled.
2923 Ä p.
161) without interruption, the action specified by the alarm
95).
2925 Ä p. 161
for the delay time configured here, an alarm
Ä Chapter 9.5.1 "Alarm Classes"
Configuration
Ä Chapter 4.5.12.2 "Load
161