Simple (function)
If TRUE, the voltage/power factor setpoint will be
raised.
Deactivated by default.
[00.24] Lower voltage/power factor setpoint
If TRUE, the voltage/power factor setpoint will be
lowered.
Deactivated by default.
[00.25] Frequency droop active
If TRUE, the frequency droop is enabled.
TRUE once missing members are detected on
the load share bus.
Not available in operating mode "STOP".
[00.26] Voltage droop active
If TRUE, the voltage droop is enabled.
TRUE once missing members are detected on
the load share bus.
Not available in operating mode "STOP".
[00.28] Critical mode
If TRUE, the control performs a critical mode
operation.
Deactivated by default.
TRUE, if no start failure is present and/or dis‐
crete input [DI 01] is not energized.
Not available in operation modes "STOP" and
"MAN".
[00.29] Firing speed reached
37535B
Extended (configuration)
easYgen-2200/2500 | Genset Control
LogicsManager Reference > Factory Settings
Appendix
Result
FALSE
FALSE
dependent on
missing mem‐
bers
dependent on
missing mem‐
bers
dependent on
start failure
and [DI 01]