Woodward easYgen-2000 Series User Manual page 461

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

Data transmission engine control
unit (ECU)
Special Deutz EMR2/Volvo EDC4
messages
Type
Engine stop information
0
No or no special engine stop
1
Engine shutdown for engine protection
2
CAN message engine stop request
3
Oil pressure too low
4
Oil level too low
5
Coolant temperature too high
6
Coolant level too low
7
Intake manifold temperature
8
Reserved (Stop via SAE-J1587)
9
Reserved (Stop via VP2)
Table 94: Special EMR2 messages
Special Scania S6 messages
Suspect parameter
Parameter group
number
number
DLN2-Proprietary
65409 (FF81h)
37535B
If the total engine hours sent by the ECU exceed
1
419,000 hrs, the display in the unit is not correct any‐
more
If the sent values exceed the limits of the specification, the dis‐
n
played value is not defined.
If a value of the ECU is not sent or sent as not available or
n
defective, the value will be displayed as indicated in the table
before.
Suspect parameter
number
Engine stop
Description
Assessed messages:
n
Low engine oil level
n
High engine oil level
n
Low oil pressure
n
High coolant temperature
easYgen-2200/2500 | Genset Control
Interfaces And Protocols
J1939 Protocol > Displayed Messages (Visual...
Parameter group
number
65301 (FF15h)
Display in unit
Type 0
Type 1
Type 2
Type 3
Type 4
Type 5
Type 6
Type 7
Type 8
Type 9
Display in unit
No
Missing
Yes
Description
As Type 0 to 9
Display in ToolKit
Type 0
Type 1
Type 2
Type 3
Type 4
Type 5
Type 6
Type 7
Type 8
Type 9
Display in ToolKit
No
Missing
Yes
461