Examples
Exceeding a limit value
Faling below a limit value
ID
Parameter
2400
Monitoring
2406
2404
Limit
2410
2405
Delay
2411
2401
Alarm class
2407
37535B
Configure Monitoring > Generator > Generator Unbalanced Load ...
Current in phase L1 = current in phase L3
n
Current in phase L2 has been exceeded
n
P
= tripping value percentage (example 10 %)
n
A
I
= rated current (example 300 A)
n
N
Tripping value for phase L2:
I
≥ (3 * I
n
L2
= (3 * 300 A * 10 % + 300 A + 300 A) / 2
= ((3 * 300 A * 10) / 100 + 300 A + 300 A) / 2
= 345 A
Current in phase L2 = current in phase L3
n
Current in phase L1 has been undershot
n
P
= tripping value percentage (example 10 %)
n
A
I
= rated current (example 300 A)
n
N
Tripping value for phase L1:
I
≤ (I
n
L1
= (300 A + 300 A - 3 * 300 A * 10 %) / 2
= (300 A + 300 A - (3 * 300 A * 10) / 100)) / 2
= 255 A
CL
Setting range
Description
[Default]
2
[On]
Unbalanced load monitoring is carried out according to the following parame‐
ters. Monitoring is performed at two levels.
Both values may be configured independent from each other (condition:
Level 1 < Level 2).
Off
No monitoring is carried out for either Level 1 limit or Level 2 limit.
2
0.0 to 100.0 %
The percentage values that are to be monitored for each threshold limit are
defined here.
2404: [10.0 %]
If this value is reached or exceeded for at least the delay time without inter‐
2410: [15.0 %]
ruption, the action specified by the alarm class is initiated.
Notes
This value refers to the "Generator rated current" (parameter
2
0.02 to 99.99 s
If the monitored current exceeds the threshold value for the delay time config‐
ured here, an alarm will be issued.
2405: [10.00 s]
2411: [1.00 s]
Notes
If the monitored current falls below the threshold (minus the hysteresis)
before the delay expires the time will be reset.
2
Class A/B/C/D/
Each limit may be assigned an independent alarm class that specifies what
E/F
action should be taken when the limit is surpassed.
2401: [B]
2407: [E]
easYgen-2200/2500 | Genset Control
* P
+ I
+ I
) / 2
N
A
L1
L3
+ I
- 3 * I
* P
) / 2
L2
L3
N
A
Configuration
1754 Ä p.