ID
Parameter
5552
Gain factor
5553
Expand dead‐
band factor
5554
Delay expand
deadband
5518
Frequency set‐
point 1 source
37535B
Configure Application > Configure Controller > Frequency Control
CL
Setting range
Description
[Default]
1
0.1 to 10.0
The gain factor K
[5.0]
By increasing the number configured in this parameter, the operating time of
the relay will be in-creased in response to a deviation from the frequency ref‐
erence.
By increasing the gain, the response is increased to permit larger corrections
to the variable to be controlled. The farther out of tolerance the process is the
larger the response action is to return the process to the tolerance band.
Notes
If the gain is configured too high, the result is excessive overshoot/undershoot
of the desired value.
This parameter is only visible if frequency control (parameter
is configured to "3pos controller".
1
1.0 to 9.9
If the measured generator frequency is within the deadband range (param‐
eter
[1.0]
eter
configured here.
Notes
This parameter is only visible if frequency control (parameter
is configured to "3pos controller".
1
1.0 to 9.9 s
The measured generator frequency must be within the deadband range for
the time configured here in order to multiply the deadband with the factor con‐
[2.0 s]
figured in parameter
Notes
This parameter is only visible if frequency control (parameter
is configured to "3pos controller".
2
Determined by
The Frequency setpoint 1 source may be selected from the available data
AnalogManager
sources.
Though it is possible to select from all available data sources
Ä Chapter 9.3.1 "Data Sources" on page 533 ), only the following data
(
sources may be used:
[05.01]
Internal frequency setpoint 1
Internal frequency control setpoint 1 (parameter
setpoint 1
05.02
Internal frequency setpoint 2
Internal frequency control setpoint 2 (parameter
setpoint 1
05.03
Interface frequency setpoint
The setpoint, which is transmitted via the interface, is used as setpoint
05.13
Discrete raise/lower frequency
The setpoint from the discrete raise/lower frequency function is used as set‐
point
06.01
Analog input 1
Analog input 1 is used to control the setpoint
06.02
Analog input 2
Analog input 2 is used to control the setpoint
easYgen-2200/2500 | Genset Control
influences the operating time of the relays.
p
5550 Ä p.
272) and the configured delay expand deadband time (param‐
5554 Ä p.
273) expires, the deadband will be multiplied with the factor
5553 Ä p.
273.
Configuration
5507 Ä p.
271)
5507 Ä p.
271)
5507 Ä p.
271)
5500 Ä p.
274) is used as
5501 Ä p.
275) is used as
273