Installation
Setup Connections > Analog Inputs
Terminal
Description
Common
N.O.
A
B
Form A
82
83
Relay output [R 08]
84
85
Relay output [R 09]
86
87
Relay output [R 10]
88
89
Relay output [R 11]
Terminal
Common
N.C.
N.O.
A
B
C
38
39
40
3.2.12

Analog Inputs

72
All
All
All
Description
Form C
Relay output [R 05]
configurable via LogicsManager
1
Notes
It is recommended to use two-pole analog senders. This ensures
an accuracy of ≤ 1 % for 0 to 500 Ohm inputs and ≤ 1.2 % for 0 to
20 mA inputs.
The following senders may be used for the analog inputs:
0 to 20 mA
n
Resistive (0 to 500 Ohm)
n
easYgen-2200/2500 | Genset Control
Preconfigured to "Command: close MCB" or Logi‐
csManager
1
LogicsManager
1
LogicsManager
1
LogicsManager
1
Preconfigured to "Command: open MCB"
LogicsManager: Using the function LogicsMan‐
ager it is possible to freely program the relays for
all appliction modes.
: no breaker mode;
: GCBopen
: GCB
: GCB/MCB
N.O.: normally open (make) contact
N.C.: normally closed (break) contact