Application
Modbus Applications > Remote Control > Setpoint Setting
Example 1: Start Request
Fig. 201: Modbus - write register -
Example 2: Stop Request
Fig. 202: Modbus - write register -
Example 3: External Acknowledge
Fig. 203: Modbus - write register -
external acknowledge
6.6.1.2

Setpoint Setting

Fig. 204: Setpoint source configura‐
ID
Parameter
507
Active Power Setpoint
508
Power Factor Setpoint
428
By double-clicking the address, a Write Register command may be
issued.
Fig. 201 shows how bit 0 is set using the ModScan32 Software.
start request
By double-clicking the address, a Write Register command may be
issued.
Fig. 202 shows how bit 1 is set using the ModScan32 Software.
stop request
By double-clicking the address, a Write Register command may be
issued.
Fig. 203 shows how bit 4 is set using the ModScan32 Software.
For a remote setting of the control setpoints, it is necessary to use
the interface setpoints instead of the internal setpoints.
For example, use data source "05.06 Interface pwr. setp." in
parameter
load setpoint via interface.
No password is required to write this value. shows an exemplary
tion
configuration of the load setpoint 1 source. All other setpoint
sources are configured accordingly.
The interface setpoints may be set using the objects for active
power, power factor, frequency, and voltage (refer to
Ä Chapter 9.2.3 "Additional Data Identifier" on page 527 for
detailed information).
Setting range
0 to 999999
-710 to 1000 to
710
easYgen-2200/2500 | Genset Control
5539 Ä p. 278
(Load setpoint 1 source) to transmit a
Unit
Data type
1/10 kW
INTEGER 32
-
INTEGER 16
Data source
05.06
05.12
37535B