Woodward easYgen-2000 Series User Manual page 380

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

Application
Special Applications > Performing Remote Start/St... > Remote Start/Stop And Ackn...
Fig. 156: LogicsManager function
"Start req in AUTO"
External acknowledgement
Fig. 157: LogicsManager function
"Ext. acknowledge"
380
3.
Configure the LogicsManager function "Start req in AUTO" as
shown in (Fig. 156).
ð With this setting, the "Start req in AUTO" LogicsManager
output becomes TRUE as soon as the remote request
signal is enabled.
The LogicsManager commands 2 and 3 may be used
to configure additional conditions like discrete inputs,
which must be energized to be able to issue the
remote start request.
1.
Either on the front panel or using ToolKit navigate to menu
"Configure monitoring è Miscellaneous" .
2.
Open the LogicsManager for entry "Ext. acknowledge".
3.
Configure the LogicsManager function "Ext. acknowledge" as
shown in (Fig. 157).
ð With this setting, the "Ext. acknowledge" LogicsManager
output becomes TRUE as soon as the remote acknowl‐
edge signal is enabled.
The LogicsManager commands 2 and 3 may be used
to configure additional conditions like discrete inputs,
which must be energized to be able to issue the
remote acknowledge command.
Ä Chapter 6.6 "Modbus Applications" on page 427
Please refer to
for a description of how to configure the LogicsManager functions
via Modbus.
All interfaces access the same bits. The command var‐
iable "04.13 Remote request" remains enabled in the
easYgen until a new command is sent or the power
supply failed or is removed.
Remote start:
The command variable "04.13 Remote request" changes to "1"
n
(high) if the start bit (ID 503, bit 0) changes from "0" to "1".
The command variable "04.13 Remote request" changes to "0"
n
(low) if the stop bit (ID 503, bit 1) changes from "0" to "1"
(Fig. 158).
easYgen-2200/2500 | Genset Control
37535B