Analog Manager Reference > Reference Values > Rated Frequency
Analog output example
Flexible limit example
9.3.2.2

Mains Rated Voltage

Analog output example
Flexible limit example
9.3.2.3

Rated Frequency

540
The generator rated voltage (parameter
n
configured to 400 V.
The source value at maximum output is configured to 110.00
n
% (of the rated voltage i.e. 440 V).
The source value at minimum output is configured to 10.00
n
% (of the rated voltage i.e. 40 V).
The analog output range is configured to 0 to 20 mA.
n
If a generator voltage of 40 V (or below) is measured, the
n
analog output issues its lower limit (i.e. 0 mA).
If a generator voltage of 440 V (or above) is measured, the
n
analog output issues its upper limit (i.e. 20 mA).
If a generator voltage of 240 V is measured, the analog
n
output issues 50 % of its upper limit (i.e. 10 mA).
If a generator voltage of 400 V is measured, the analog
n
output issues 90 % of its upper limit (i.e. 18 mA).
The generator rated voltage (parameter
n
configured to 400 V.
If the flexible limit is to be configured to 110.00 % (of the
n
rated voltage i.e. 440 V), it must be entered as 11000.
All mains voltage values (wye, delta, average, and peak values)
refer to the mains rated voltage (parameter
The mains rated voltage (parameter
n
ured to 400 V.
The source value at maximum output is configured to 110.00
n
% (of the rated voltage i.e. 440 V).
The source value at minimum output is configured to 10.00
n
% (of the rated voltage i.e. 40 V).
The analog output range is configured to 0 to 20 mA.
n
If a mains voltage of 40 V (or below) is measured, the
n
analog output issues its lower limit (i.e. 0 mA).
If a mains voltage of 440 V (or above) is measured, the
n
analog output issues its upper limit (i.e. 20 mA).
If a mains voltage of 240 V is measured, the analog output
n
issues 50 % of its upper limit (i.e. 10 mA).
If a mains voltage of 400 V is measured, the analog output
n
issues 90 % of its upper limit (i.e. 18 mA).
The mains rated voltage (parameter
n
ured to 400 V.
If the flexible limit is to be configured to 110.00 % (of the
n
rated voltage i.e. 440 V), it must be entered as 11000.
All frequency values (generator, mains, busbar 1) refer to the rated
system frequency (parameter
easYgen-2200/2500 | Genset Control
1766 Ä p.
1766 Ä p.
1768 Ä p.
1768 Ä p.
95) is config‐
1768 Ä p.
95) is config‐
1750 Ä p.
94).
95) is
95) is
95).
37535B

Advertisement

Table of Contents
loading

Table of Contents