Appendix
Analog Manager Reference > Reference Values > Display Value Format
9.3.2.14
Battery Voltage
Analog output example
Flexible limit example
9.3.2.15
Busbar 1 Rated Voltage
Analog output example
Flexible limit example
9.3.2.16
Display Value Format
548
The measured battery and auxiliary excitation voltage refer to the
fix rated battery voltage of 24 V.
The source value at maximum output is configured to 120.00
n
% (of the rated voltage i.e. 28.8 V).
The source value at minimum output is configured to 20.00
n
% (of the rated voltage i.e. 4.8 V).
The analog output range is configured to 0 to 20 mA.
n
If a battery voltage of 4.8 V (or below) is measured, the
n
analog output issues its lower limit (i.e. 0 mA).
If a battery voltage of 28.8 V (or above) is measured, the
n
analog output issues its upper limit (i.e. 20 mA).
If a battery voltage of 16.8 V is measured, the analog output
n
issues 50 % of its upper limit (i.e. 10 mA).
If a battery voltage of 24 V is measured, the analog output
n
issues 80 % of its upper limit (i.e. 16 mA).
If the flexible limit is to be configured to 120.00 % (of the
n
rated voltage i.e. 28.8 V), it must be entered as 12000.
The busbar 1 delta voltage values refer to the busbar 1 rated
voltage (parameter
The busbar 1 rated voltage (parameter
n
figured to 400 V.
The source value at maximum output is configured to 110.00
n
% (of the rated voltage i.e. 440 V).
The source value at minimum output is configured to 10.00
n
% (of the rated voltage i.e. 40 V).
The analog output range is configured to 0 to 20 mA.
n
If a busbar 1 voltage of 40 V (or below) is measured, the
n
analog output issues its lower limit (i.e. 0 mA).
If a busbar 1 voltage of 440 V (or above) is measured, the
n
analog output issues its upper limit (i.e. 20 mA).
If a busbar 1 voltage of 240 V is measured, the analog
n
output issues 50 % of its upper limit (i.e. 10 mA).
If a busbar 1 voltage of 400 V is measured, the analog
n
output issues 90 % of its upper limit (i.e. 18 mA).
The busbar 1 rated voltage (parameter
n
figured to 400 V.
If the flexible limit is to be configured to 110.00 % (of the
n
rated voltage i.e. 440 V), it must be entered as 11000.
The analog input values refer to the display value format (refer to
parameter
1035 Ä p.
easYgen-2200/2500 | Genset Control
1781 Ä p.
95).
1781 Ä p.
1781 Ä p.
215).
95) is con‐
95) is con‐