Woodward easYgen-2000 Series User Manual page 449

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

Modbus Applications > Changing Parameter Settings > Remotely Resetting The Def...
Fig. 239: Write register - enable the
resetting procedure via RS-232/
RS-485
Example 2 (reset to default)
37535B
Fig. 238: Modscan32 at address 410418
1.
Use the "display options" to set the value format to decimal.
2.
Double-click the address to issue a Write Register com‐
mand.
ð Fig. 239 shows how the parameter is enabled using the
ModScan32 Software. The value must be set to "1" to
enable the parameter.
In order to reset the default values, parameter
be enabled.
The default values shall be reset.
Modbus address = 40000 + (Par. ID + 1) = 41702
n
Modbus length = 1 (UNSIGNED 16)
n
easYgen-2200/2500 | Genset Control
Application
1701 Ä p. 92
must
449