Setup Connections > Voltage Measuring > Mains Voltage
3.2.5.2.4
Parameter Setting '1Ph 2W' (1-phase, 2-wire)
'1Ph 2W' Phase-Neutral Measuring
Mains windings
Table 15: Mains windings - 1Ph 2W (phase neutral)
Measuring inputs
Terminal assignment
1Ph 2W
Wiring terminals
Rated voltage (range)
120 V (50 to 130 V
Measuring range (max.)
0 to 150 Vac
Terminal
A
22
Phase
L1
54
The 1-phase, 2-wire measurement may be performed
phase-neutral or phase-phase.
Please note to configure and wire the easYgen
consistently.
Fig. 35: Measuring inputs - 1Ph 2W (phase neutral)
)
eff.
C
E
G
24
26
28
N
N
N