Configuring the analog input for a
ripple control receiver
ID
Parameter
1000
Type
1001
User defined min
display value
1002
User defined
max display
value
1039
Sender value at
display min.
1040
Sender value at
display max.
1020
Sender type
10113
Filter time con‐
stant
3632
Bargraph min‐
imum
3633
Bargraph max‐
imum
ID
Parameter
1025
Description
1035
Value format
Configuring the derating of power
ID
Parameter
15143
Start derating at
15144
Stop derating at
15145
Max. power devi‐
ation
15147
Source free
derating
37535B
1.
Either on the front panel or using ToolKit navigate to menu
"Configure analog inputs è Analog input 1" .
2.
Configure the parameters listed below.
Value
Comment
Linear
A user-defined linear characteristic curve is to be used
+00000
A value of 000.00 % is displayed at the minimum of the input range
+01000
A value of 100.00 % is displayed at the maximum of the input range
000.00 %
The sender value at minimum display is 0 % i.e. 0 Ohms
100.00 %
The sender value at maximum display is 100 % i.e. 500 Ohms
0 - 500 Ohm
A 0 to 500 Ohms sender is used on the analog input
3
Filter time depending on the ambient conditions
+00000
The start value for the bargraph display of the analog input is 00000
+01000
The end value for the bargraph display of the analog input is 01000
3.
Configure the following parameters using ToolKit. They facili‐
tate a more detailed display of the analog value.
Value
Comment
Analog inp. 1
Analog input [AI 01] is labeled with "Analog inp.1" on the display
000.00 %
The value format of the bargraph display of the analog input is "000.00 %"
1.
Either on the front panel or using ToolKit navigate to menu
"Configure load control è Derating of power" .
2.
Configure the parameters listed below.
Value
Comment
+01000
The starting point when the derating becomes active
+00000
Defines (in combination with parameter
derating function
100.0 %
The maximal power deviation of the derating function
06.01 Analog
Defines the analog source which controls the derating function
input 1
easYgen-2200/2500 | Genset Control
Special Applications > Ripple Control Receiver
15143 Ä p.
Application
283) the ramp of the
405