Configuration
Configure Monitoring > Miscellaneous > J1939 Interface - Amber Wa...
ID
Parameter
15119
Delay
15116
Alarm class
15117
Self acknowl‐
edge
15118
Delayed by
engine speed
4.4.6.7

J1939 Interface - Amber Warning Alarm

General notes
ID
Parameter
15120
Monitoring
15124
Delay
184
CL
Setting range
Description
[Default]
2
0 to 999 s
The red stop lamp delay is configured with this parameter.
[2 s]
If the ECU sends the Red Stop Lamp On message, the action specified by
the alarm class is initiated after the delay configured here expires.
2
Class A/B/C/D/
Each limit may be assigned an independent alarm class that specifies what
E/F/Control
action should be taken when the limit is surpassed.
[A]
Notes
For additional information refer to
on page 587
2
[Yes]
The control unit automatically clears the alarm if the fault condition is no
longer detected.
No
The control unit does not automatically reset the alarm when the fault condi‐
tion is no longer detected.
The alarm must be acknowledged and reset by manually pressing the appro‐
priate buttons or by activating the LogicsManager output "External acknowl‐
edgement" (via a discrete input or via an interface).
2
Yes
Monitoring for fault conditions is not performed until engine delayed moni‐
toring is enabled. The engine monitoring delay time (param‐
eter
parameters assigned this delay.
[No]
Monitoring for this fault condition is continuously enabled regardless of engine
speed.
This watchdogs monitors, whether a specific alarm bit is received
from the CAN J1939 interface. This enables to configure the
easYgen in a way that a reaction is caused by this bit (e.g.
warning, shutdown).
CL
Setting range
Description
[Default]
2
On
Monitoring of the Amber Warning Lamp message from the ECU is carried out
according to the following parameters.
[Off]
Monitoring is disabled.
2
0 to 999 s
The amber warning lamp delay is configured with this parameter.
[2 s]
If the ECU sends the Amber Warning Lamp On message, the action specified
by the alarm class is initiated after the delay configured here expires.
easYgen-2200/2500 | Genset Control
Ä Chapter 9.5.1 "Alarm Classes"
3315 Ä p.
239) must expire prior to fault monitoring being enabled for
If this protective function is triggered, the display indi‐
cates "Amber warning lamp" and the logical command
variable "05.14" will be enabled.
37535B