Woodward easYgen-2000 Series User Manual page 463

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

Remote
1
2
control
parameter
Engine Start No
Yes
Engine Stop
Yes
Yes
Droop mode Yes
Yes
37535B
Supported ECUs
1
- Woodward EGS
2
- Scania S6
3
- Deutz EMR2/EMR3 / Volvo EDC4
4
- Volvo EMS2
5
- Volvo EMS1/EDC3
6
- MTU ADEC ECU7
7
- MAN MFR/EDC7
8
- Standard
9
- SISU EEM 2/3
10 - Cummins
11 - MTU ADEC ECU8
3
4
5
6
7
No
Yes
Yes
Yes
Yes
No
Yes
Yes
Yes
Yes
No
Yes
Yes
Yes
Yes
easYgen-2200/2500 | Genset Control
J1939 Protocol > Supported J1939 ECUs & Rem...
Please note that some ECU manufacturers require that
this functionality must be enabled first. In some cases,
this is only possible by the manufacturer. Please con‐
sider this when ordering the ECU.
8
9
10
11
No
No / Yes Yes
Yes
Yes
No / Yes Yes
Yes
Yes
Yes /
Yes
No
Yes
Interfaces And Protocols
Comment
If an engine start command is initi‐
ated by the easYgen, this informa‐
tion is transmitted in the form of a
J1939 message bit to an ECU. If
ignition speed is reached, this bit
will be reset (LogicsManager com‐
mand variable 03.02. "Starter").
This J1939 bit information is set, if
a "Stop" command in automatic or
manual mode is present in the
easYgen. The "Stop" bit informa‐
tion remains set, until ignition
speed is fallen below. After igni‐
tion speed has been fallen below,
the "Stop" bit will be reset (Logi‐
csManager command variable
03.27. "Stopping solenoid").
This J1939 bit information is set, if
a "Start" command in automatic or
manual mode is initiated by the
easYgen. The bit remains set until
the engine has been stopped.
Note
This message is only sent, if the
LogicsManager output 00.25 "Fre‐
quency droop active" is TRUE.
463