Woodward easYgen-2000 Series User Manual page 480

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

Technical Specifications
Accuracy
Measuring value
Display
Phase angle
-180 to 180°
Analog inputs
0 to 180 Ohms
Freely scaleable
0 to 360 Ohms
Freely scaleable
0 to 500 Ohms
Freely scaleable
0 to 20 mA
Freely scaleable
Reference conditions
480
Accuracy
1 % / 2.5 %
4
(of
500 Ohms)
1 % / 2.5 %
4
(of 20 mA)
1
Setting of the parameter for the PT secondary rated
voltage
2
Depending on the used measuring inputs
(120/480 V)
3
Depending on the CT input hardware (1/5 A) of the
respective unit
For two-pole senders only / for single-pole senders
4
and a combination of single- and two-pole sensors
The reference conditions for measuring the accuracy
are listed below.
Input voltage
Input current
Frequency
Power supply
Power factor (cos φ)
Ambient temperature
Warm-up period
easYgen-2200/2500 | Genset Control
Measuring start
Notes
1.25 % (of PT secondary
180° is displayed for
volt. setting)
measuring values below
measuring start
For VDO sensors
For VDO sensors
For resistive sensors
Sinusoidal rated voltage
Sinusoidal rated current
Rated frequency +/- 2 %
Rated voltage +/- 2 %
1.00
23 °C +/- 2 K
20 minutes
37535B