Woodward easYgen-2000 Series User Manual page 356

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

Operation
Change Operating Modes > Operating Mode AUTOMATIC
Start engine
Auto mains failure operation (AMF)
356
The function of the easYgen depends on the configu‐
ration of the unit and how the external signals are
used.
Use the softkey
AUTOMATIC.
ð This symbol indicates, that operating mode AUTOMATIC
is selected.
For a more detailed description of the start/stop
sequence of the engine and the associated parame‐
ters refer to Ä Chapter 4.5.11 "Automatic Run"
on page 246.
The main functions are briefly described in the fol‐
lowing sections.
The engine is started via a remote start signal.
Prerequisites:
The AUTOMATIC operating mode is enabled.
n
The start request is enabled by the LogicsManager "Start req.
n
in AUTO".
No shut down alarm is present. (for explanation of the alarm
n
classes refer to
on page 587 ).
The engine is ready for operation.
n
The GCB is open.
n
Auto mains failure operation is only available in appli‐
cation mode
If the AUTOMATIC operating mode is enabled and the mains fail,
the engine and the power circuit breakers will be operated
according to the current application mode.
Prerequisites:
The AUTOMATIC operating mode is enabled.
n
The parameter "Emergency power" is configured to "On".
n
The configured mains failure limits are reached.
n
The configured delay times have expired.
n
No shut down alarm is present. (for explanation of the alarm
n
classes refer to
on page 587 ).
The engine is ready for operation.
n
easYgen-2200/2500 | Genset Control
"AUTO Mode" to activate operating mode
Ä Chapter 9.5.1 "Alarm Classes"
.
Ä Chapter 9.5.1 "Alarm Classes"
37535B