Woodward easYgen-2000 Series User Manual page 116

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

Configuration
Configure Monitoring > Generator > Generator Reverse/Reduced ...
Example
Example
Example
ID
Parameter
2250
Monitoring
2256
2254
Limit
2260
2255
Delay
2261
116
Level 1 limit = Positive and Level 2 limit = Positive
n
(whereas Level 1 limit > Level 2 limit > 0 %)
Both limits are configured for reduced power monitoring.
n
Rated power is 100 kW, Level 1 limit = 5 % > Level 2 limit =
n
3 %
Rripping if real power falls below 5 kW (Level 1 limit) or 3 kW
n
(Level 2 limit)
Level 1 limit = Negative and Level 2 limit = Negative
n
(whereas Level 2 limit < Level 1 limit < 0 %)
Both limits are configured for reverse power monitoring.
Rated power is 100 kW, Level 1 limit = -3 % > Level 2 limit =
n
-5 %
Tripping if real power falls below -3 kW (Level 1 limit)
n
or -5 kW (Level 2 limit)
Level 1 limit = Positive and Level 2 limit = Negative
n
(whereas Level 1 limit > 0 % > Level 2 limit)
Level 1 is configured for reduced power monitoring and
n
Level 2 is configured for reverse power monitoring.
n
Rated power is 100 kW, Level 1 limit = 3 % > Level 2 limit =
n
-5 %
Tripping if real power falls below 3 kW (Level 1 limit)
n
or -5 kW (Level 2 limit)
CL
Setting range
Description
[Default]
2
[On]
Reverse/reduced power monitoring is carried out according to the following
parameters.
Both values may be configured independent from each other (prerequisite for
Off
Monitoring is disabled for Level 1 limit and/or Level 2 limit.
2
-99.9 to 99.9 %
The percentage values that are to be monitored for each threshold limit are
defined here.
2254: [-3.0 %]
If this value is reached or fallen below for at least the delay time without inter‐
2260: [-5.0 %]
ruption, the action specified by the alarm class is initiated.
Notes
This value refers to the Generator rated active power (parameter
1752 Ä p.
2
0.02 to 99.99 s
If the monitored generator power falls below the threshold value for the delay
time configured here, an alarm will be issued.
2255: [5.00 s]
2261: [3.00 s]
Notes
If the monitored generator power exceeds or falls below the threshold (plus/
minus the hysteresis) again before the delay expires the time will be reset.