Application
Modbus Applications > Changing Parameter Settings > Configuration Of LogicsMan...
6.6.2.4.3
Configuration Of Remote Start/Stop And Acknowledgement
6.6.2.4.4
Configuration Of LogicsManager Function "Start Request in AUTO"
442
* see Ä "Hex code equivalents of the logic equations'
nibbles" Table on page 436 for reference
Fig. 227: Modscan32 at address 12511
Copy the complete message of 7 words to address 12511 ff
(12510+1) in one step.
This is shown in (Fig. 227) using the ModScan32 software.
If an shutdown alarm of alarm class C through F
occurs in AUTOMATIC operating mode, the control
does not return to STOP operating mode if the alarm is
cleared after acknowledgement. This means that a
restart is initiated.
Refer to Ä Chapter 6.4.4 "Performing Remote Start/
Stop And Acknowledgement" on page 376 for detailed
information.
The easYgen may be started, stopped, or acknowledged with
CAN/Modbus. Therefore, two logical command variables have to
be configured with the LogicsManager:
04.13 Remote request
n
04.14 Remote acknowledge
n
The "Start req. in AUTO" LogicsManager function (parameter
12120 Ä p.
246) can be configured in a way that a start request in
AUTOMATIC operating mode is enabled as soon as a remote
request is issued.
Ä Chapter 6.4.4 "Performing Remote Start/Stop And
Refer to
Acknowledgement" on page 376 for information on configuration
via HMI or ToolKit.
easYgen-2200/2500 | Genset Control
37535B