Interfaces And Protocols
Load Sharing
7.7
Load Sharing
General information
Measures to reduce the bus load
Load diagnosis
470
The Modbus RTU response time can increase under
certain conditions:
–
Display refresh of easYgen-2200/2500 without
CAN (J1939 protocol) connected -> max. 2 sec‐
onds
Display refresh of easYgen-2200/2500 with CAN
–
(J1939 protocol) connected -> max. 3 seconds
Woodward recommends to make a break time of 10
ms after receiving the data of the last Modbus request.
The maximum number of participating easYgen-2000 Series
devices for load sharing is 16. The CANopen bus load increases
with the number of units participating in load sharing.
The following parameters affect the bus load:
Number of CAN participants
n
Baud rate
n
Transfer rate of load share messages
n
Visualization
n
We recommend to consider whether all data has to be sent on the
CAN bus when planning the CAN bus. It is also possible to send
visualization data via RS-485 for example.
If you need to reduce the bus load of the load share CAN bus, the
following measured may be used:
Increase the baud rate (parameter
n
sideration of the bus length (refer to
length" on page 81 ).
Reduce the transfer rate of the load share message (param‐
n
eter
9921 Ä p.
Reduce the transfer rate of the visualization message, i.e. the
n
event timer (parameter
Disable the transmission visualization data on the CAN bus
n
and use the RS-485 interface to transmit visualization data.
Disable SYNC message (parameter
n
TIME message (parameter
heartbeat time SYNC message (parameter
possible.
Multiple units on the CAN bus may cause a high bus load
depending on the used protocols and baud rate.
The easYgen provides a diagnosis screen to monitor the actual
load on the CAN bus.
To access the screen navigate to
CAN Load diagnostic" .
è
easYgen-2200/2500 | Genset Control
3156 Ä p.
Ä "Maximum CAN bus
322).
9604 Ä p.
316).
9100 Ä p.
9101 Ä p.
310) and/or the producer
"Miscellaneous
309) under con‐
310) and/or
9120 Ä p.
310), if
37535B