Installation
Setup Connections > Current Measuring > Mains Current
3.2.6.2
Mains Current
General notes
Schematic and terminals
64
Wiring terminals
Terminal
4
Phase
---
WARNING!
Dangerous voltages due to missing load
–
Before disconnecting the device, ensure that the
current transformer (CT) is short-circuited.
Generally, one line of the current transformers secon‐
dary must be grounded close to the CT.
Fig. 46: Current measuring - generator - wiring
Terminal
A
9
B
8
Table 24: Current measuring - mains - terminal assignment
easYgen-2200/2500 | Genset Control
5
4
6
---
---
---
Description
Mains current - transformer ter‐
minal s1 (k)
Mains current - transformer ter‐
minal s2 (l)
4
7
s2 (l) L3 s1 (k)
L3
A
max
2.5 mm²
2.5 mm²
37535B