Message text
Meaning
ID
Gen. overload IOP 2
Generator overload IOP, limit value 2
2315
The generator power has exceeded the limit value 2 for generator overload in isolated operation (MCB is
open) for at least the configured time and does not fall below the value of the hysteresis.
Gen. overload MOP 1
Generator overload MOP, limit value 1
2362
The generator power has exceeded the limit value 1 for generator overload in mains parallel operation
(GCB and MCB are closed) for at least the configured time and does not fall below the value of the hyste‐
resis.
Gen. overload MOP 2
Generator overload MOP, limit value 2
2363
The generator power has exceeded the limit value 2 for generator overload in mains parallel operation
(GCB and MCB are closed) for at least the configured time and does not fall below the value of the hyste‐
resis.
Gen. overvoltage 1
Generator overvoltage, limit value 1
2012
The generator voltage has exceeded the limit value 1 for generator overvoltage for at least the configured
time and does not fall below the value of the hysteresis.
Gen. overvoltage 2
Generator overvoltage, limit value 2
2013
The generator voltage has exceeded the limit value 2 for generator overvoltage for at least the configured
time and does not fall below the value of the hysteresis.
Gen. rev/red. pwr. 1
Generator reverse power, limit value 1 / Generator reduced power, limit value 1
2262
The generator power has exceeded the limit value 1 for generator reverse power / generator reduced
power for at least the configured time and does not fall below the value of the hysteresis.
Gen. rev/red. pwr. 2
Generator reverse power, limit value 2 / Generator reduced power, limit value 2
2263
The generator power has exceeded the limit value 2 for generator reverse power / generator reduced
power for at least the configured time and does not fall below the value of the hysteresis.
Gen. ph. rot. mismatch
Generator rotating field mismatch
3955
The generator rotating field does not correspond with the configured direction.
Gen. underfrequency 1
Generator underfrequency, limit value 1
1962
The generator frequency has fallen below the limit value 1 for generator underfrequency for at least the
configured time and has not exceeded the value of the hysteresis. Additionally, the alarm has not been
acknowledged (unless the "Self acknowledgement" is configured YES).
Gen. underfrequency 2
Generator underfrequency, limit value 2
1963
The generator frequency has fallen below the limit value 2 for generator underfrequency for at least the
configured time and has not exceeded the value of the hysteresis.
Gen. undervoltage 1
Generator undervoltage, limit value 1
2062
The generator voltage has fallen below the limit value 1 for generator undervoltage for at least the config‐
ured time and has not exceeded the value of the hysteresis.
Gen. undervoltage 2
Generator undervoltage, limit value 2
2063
The generator voltage has fallen below the limit value 2 for generator undervoltage for at least the config‐
ured time and has not exceeded the value of the hysteresis.
Gen unloading fault
Generator unloading mismatch
3124
The easYgen failed to reduce the generator power below the configured unload limit within the configured
time.
Gen. volt. asymmetry
Voltage asymmetry
3907
The generator phase-to-phase voltages have higher differences between each other than the configured
limit value.
37535B
Event And Alarm Reference > Event History > Alarm Messages
easYgen-2200/2500 | Genset Control
Appendix
595