Flexible limit example
9.3.2.7

Mains Rated Reactive Power

Analog output example
Flexible limit example
9.3.2.8

Generator Rated Apparent Power

37535B
Analog Manager Reference > Reference Values > Generator Rated Apparent P...
The mains rated active power (parameter
n
configured to 500 kW.
If the flexible limit is to be configured to 120.00% (of the
n
rated active power i.e. 600 kW), it must be entered as
12000.
All mains reactive power values refer to the mains rated reactive
power (parameter
The mains rated reactive power (parameter
n
configured to 500 kvar.
The source value at maximum output is configured to 120.00
n
% (of the rated reactive power i.e. 600 kvar).
The source value at minimum output is configured to 0.00 %
n
(of the rated reactive power i.e. 0 kvar).
The analog output range is configured to 0 to 20 mA.
n
If a reactive power of 0 kvar is measured, the analog output
n
issues its lower limit (i.e. 0 mA).
If a reactive power of 600 kvar (or above) is measured, the
n
analog output issues its upper limit (i.e. 20 mA).
If a reactive power of 300 kvar is measured, the analog
n
output issues 50 % of its upper limit (i.e. 10 mA).
If a reactive power of 120 kvar is measured, the analog
n
output issues 20 % of its upper limit (i.e. 4 mA).
The mains rated reactive power (parameter
n
configured to 500 kvar.
If the flexible limit is to be configured to 120.00 % (of the
n
rated reactive power i.e. 600 kvar), it must be entered as
12000.
All generator apparent power values refer to the generator rated
active power (parameter
tive power (parameter
The generator rated apparent power S is calculated using the real
power P and the reactive power Q according to this formula:
S = √(P
n
easYgen-2200/2500 | Genset Control
1746 Ä p.
95).
1752 Ä p.
1758 Ä p.
95).
+ Q
)
2
2
Appendix
1748 Ä p.
95) is
1746 Ä p.
95) is
1746 Ä p.
95) is
95) and generator rated reac‐
543