Mains Rated Voltage - Woodward easYgen-2000 Series User Manual

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

Appendix
Analog Manager Reference > Reference Values > Mains Rated Voltage
Analog output example
Flexible limit example
9.3.2.6

Mains Rated Voltage

Analog output example
542
The generator rated reactive power (param‐
n
eter
1758 Ä p.
The source value at maximum output is configured to 120.00
n
% (of the rated reactive power i.e. 600 kvar).
The source value at minimum output is configured to 0.00 %
n
(of the rated reactive power i.e. 0 kvar).
The analog output range is configured to 0 to 20 mA.
n
If a reactive power of 0 kvar is measured, the analog output
n
issues its lower limit (i.e. 0 mA).
If a reactive power of 600 kvar (or above) is measured, the
n
analog output issues its upper limit (i.e. 20 mA).
If a reactive power of 300 kvar is measured, the analog
n
output issues 50 % of its upper limit (i.e. 10 mA).
If a reactive power of 120 kvar is measured, the analog
n
output issues 20 % of its upper limit (i.e. 4 mA).
The generator rated reactive power (param‐
n
eter
1758 Ä p.
If the flexible limit is to be configured to 120.00 % (of the
n
rated reactive power i.e. 600 kvar), it must be entered as
12000.
The above example is valid for inductive/lagging
power. If capacitive/leading power is to be output, the
settings for the source value at min/max output must
be negative.
All mains active power values refer to the mains rated active power
(parameter
1748 Ä p.
The mains rated active power (parameter
n
configured to 500 kW.
The source value at maximum output is configured to
n
120.00% (of the rated active power i.e. 600 kW).
The source value at minimum output is configured to 0.00%
n
(of the rated active power i.e. 0 kW)
The analog output range is configured to 0 to 20 mA.
n
If a real power of 0 kW is measured, the analog output
n
issues its lower limit (i.e. 0 mA).
If a real power of 600 kW (or above) is measured, the analog
n
output issues its upper limit (i.e. 20 mA).
If a real power of 300 kW is measured, the analog output
n
issues 50 % of its upper limit (i.e. 10 mA).
If a real power of 120 kW is measured, the analog output
n
issues 20 % of its upper limit (i.e. 4 mA).
easYgen-2200/2500 | Genset Control
95) is configured to 500 kvar.
95) is configured to 500 kvar.
95).
1748 Ä p.
95) is
37535B