ID
Parameter
12570
Auto idle mode
12550
Constant idle
run
(Continuous idle
mode)
3328
Automatic idle
time
(Time for auto‐
matic idle mode)
3329
During emer‐
gency / critical
(Idle mode pos‐
sible during
emergency /
critical opera‐
tion)
37535B
CL
Setting range
Description
[Default]
2
Determined by
Once the conditions of the LogicsManager have been fulfilled the engine will
LogicsManager
be operated in idle mode automatically for the configured time during start-up.
Monitoring is limited as described above.
[(0 & 1) ≥ 0]
This function may always be configured to "1" for example.
Notes
For information on the LogicsManager and its default settings see
Ä Chapter 9.4.1 "LogicsManager Overview" on page 549 .
2
Determined by
As long as the conditions of the LogicsManager have been fulfilled the engine
LogicsManager
will be continuously operated in idle mode. Monitoring is limited as described
above. A key switch via a DI may be configured here for example.
[(0 & 1) & 0]
Notes
The idle mode is blocked if the GCB is already closed.
For information on the LogicsManager and its default settings see
Ä Chapter 9.4.1 "LogicsManager Overview" on page 549 .
2
1 to 9999 s
The automatic idle mode is active for the time configured here. Monitoring is
limited as described above during this time.
[30 s]
2
Yes
If an emergency or critical operation is enabled, the engine will go to rated
speed only after completing the configured idle mode.
[No]
If an emergency or critical operation is enabled, no idle run will be performed.
The engine will go directly to rated speed.
easYgen-2200/2500 | Genset Control
Configure Application > Engine > Idle Mode
The normal operation monitoring limits will be enabled
again, if one of the following conditions is fulfilled:
–
Idle mode has ended and generator frequency has
reached rated frequency -1 Hz. (e.g. 49 Hz at 50
Hz rated)
Idle mode has ended and engine delayed moni‐
–
toring (parameter
3315 Ä p.
The flexible limits 13 through 16 are disabled during
idle mode operation (Ä Chapter 4.4.5 "Flexible Limits"
on page 175).
Configuration
239) has expired.
243