Configuration
Configure Application > Configure Breakers > Parameters
4.5.1.7

Parameters

ID
Parameter
3401
Application
mode
3411
Breaker transi‐
tion mode
3412
Breaker transi‐
tion mode 1
200
CL
Setting range
Description
[Default]
2
The unit may be configured for four different application modes. The discrete
inputs and relay outputs are pre-defined dependent upon the selected appli‐
cation mode. Only the screens and functions that pertain to the application
mode selected are displayed. The single line diagram in the main screen will
change.
Refer to
None
Application mode
The control unit will function as an engine start/stop control with generator
and engine protection. All necessary inputs and outputs are assigned and
pre-defined.
GCB open
Application mode
The control unit will function as an engine start/stop control with generator
and engine protection. The control unit can only open the GCB. All necessary
inputs and outputs are assigned and pre-defined.
GCB
Application mode
The control unit will function as a 1 CB unit. The control unit performs full con‐
trol like synchronizing, opening and closing the GCB with generator and
engine protection. All necessary inputs and outputs are assigned and pre-
defined.
[GCB/MCB]
Application mode
The control unit will function as a 2 CB unit. The control unit performs full con‐
trol like synchronizing, opening and closing the GCB and the MCB with gener‐
ator and engine protection. The GCB/MCB perform also full load transfer via
open/closed transition, interchange and parallel mode. All necessary inputs
and outputs are assigned and pre-defined.
2
Parallel / Inter‐
The control unit automatically controls the two breakers (MCB and GCB).
change / Closed
Transit. / Open
Transition /
External
[Parallel]
Notes
This parameter only applies to application mode
For a detailed explanation for each mode refer to
tion Modes (Breaker Logic)" on page 195 .
The unit provides two alternative transition modes, which may be activated
temporarily via the LogicsManager and override the transition mode config‐
ured in this parameter.
2
Parallel / Inter‐
The control unit automatically controls the two breakers (MCB and GCB).
change / Closed
Transit. / Open
Transition /
External
[Parallel]
easYgen-2200/2500 | Genset Control
for additional information.
DEBUG: 2
.
Ä Chapter 4.5.1.6 "Transi‐
37535B