Group 03: Engine Control - Woodward easYgen-2000 Series User Manual

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

LogicsManager Reference > Logical Command Variables > Group 03: Engine Control
No.
ID
Name
02.12
130
Generator rota‐
tion CCW
02.13
131
Generator rota‐
tion CW
02.14
132
Mains rotation
CCW
02.15
133
Mains rotation
CW
02.16
134
Reserved
02.17
135
Reserved
02.18
136
Reserved
02.19
137
Reserved
02.20
138
Reserved
02.21
139
Busbar 1 is dead
9.4.4.4

Group 03: Engine Control

No.
ID
03.01
179
03.02
180
03.03
181
03.04
182
03.05
183
03.06
184
03.07
185
03.08
186
03.09
187
03.10
188
03.11
189
03.12
190
37535B
Function
Generator voltage: rotating direction
CCW
Generator voltage: rotating direction
CW
Mains voltage: rotating direction
CCW
Mains voltage: rotating direction CW
Busbar 1 is dead
Engine control
n
Logic command variables 03.01-03.31
n
These variables may be used as command variable in a logical
output to set parameters for customized operations.
Name / Function
Auxiliary services
Starter
Reserved
Preglow (Diesel)
Ignition (Gas)
Horn (active)
Engine released
Engine delay over (engine
delayed monitoring expired)
Breaker delay over (breaker
delayed monitoring expired)
Reserved
Reserved
Reserved
Reserved
easYgen-2200/2500 | Genset Control
Note
TRUE as long as the respective rotation field is
detected in case of a three-phase voltage measurement
at the respective measuring location
TRUE as long as the busbar voltage is below the value
configured in parameter
detection max. volt.)
Note
TRUE if an auxiliary services prerun or postrun is enabled
TRUE if the starter relay is energized
TRUE if the preglow (Diesel) or ignition (gas) relay is energized
TRUE if alarm class B to F is activated until the time until horn
reset is expired or it is acknowledged for the first time.
TRUE if the engine is requested and the start is released
TRUE after expiration of the "delayed engine monitoring" timer
until the fuel relay is de-energized
TRUE after expiration of the "breaker delay" timer until the fuel
relay is de-energized (= CB may be closed)
Appendix
5820 Ä p. 201
(Dead bus
563