Installation
Setup Connections > Current Measuring > Generator Current
3.2.6
Current Measuring
3.2.6.1
Generator Current
General notes
Schematic and terminals
62
WARNING!
Dangerous voltages due to missing load
–
Before disconnecting the device, ensure that the
current transformer (CT) is short-circuited.
Generally, one line of the current transformers secon‐
dary must be grounded close to the CT.
Fig. 43: Current measuring - generator - wiring
Terminal
A
7
B
4
C
6
D
4
E
5
F
4
Table 23: Current measuring - generator - terminal assignment
easYgen-2200/2500 | Genset Control
Description
Generator current - L3 - trans‐
former terminal s1 (k)
Generator current - L3 - trans‐
former terminal s2 (l)
Generator current - L2 - trans‐
former terminal s1 (k)
Generator current - L2 - trans‐
former terminal s2 (l)
Generator current - L1 - trans‐
former terminal s1 (k)
Generator current - L1 - trans‐
former terminal s2 (l)
A
max
2.5 mm²
2.5 mm²
2.5 mm²
2.5 mm²
2.5 mm²
2.5 mm²
37535B