Installation
Setup Connections > Current Measuring > Generator Current
3.2.6

Current Measuring

3.2.6.1

Generator Current

General notes
Schematic and terminals
62
WARNING!
Dangerous voltages due to missing load
Before disconnecting the device, ensure that the
current transformer (CT) is short-circuited.
Generally, one line of the current transformers secon‐
dary must be grounded close to the CT.
Fig. 43: Current measuring - generator - wiring
Terminal
A
7
B
4
C
6
D
4
E
5
F
4
Table 23: Current measuring - generator - terminal assignment
easYgen-2200/2500 | Genset Control
Description
Generator current - L3 - trans‐
former terminal s1 (k)
Generator current - L3 - trans‐
former terminal s2 (l)
Generator current - L2 - trans‐
former terminal s1 (k)
Generator current - L2 - trans‐
former terminal s2 (l)
Generator current - L1 - trans‐
former terminal s1 (k)
Generator current - L1 - trans‐
former terminal s2 (l)
A
max
2.5 mm²
2.5 mm²
2.5 mm²
2.5 mm²
2.5 mm²
2.5 mm²
37535B