Fig. 101: CAN bus load/var sharing, diagram
4.5.12.7.7
Parameters
ID
Parameter
5531
Active power
load share
5530
Active power
load share
5631
Reactive power
load share
37535B
Configure Application > Configure Controller > Load Share Control
CL
Setting range
Description
[Default]
2
[On]
Active power load share is enabled. When multiple generators are operating
in parallel, the real power is shared proportionally.
Off
Active power load share is disabled
2
10 to 99 %
It is possible to change the emphasis placed on maintaining control variables.
By increasing or decreasing the percentage value in this parameter, the con‐
[50 %]
trol places a higher priority on maintaining the primary or secondary control
reference variable.
If the value for this parameter is configured higher, maintaining the primary
control variable has a higher priority. If the value for this parameter is config‐
ured lower, maintaining the secondary control variable has a higher priority.
Primary control variable
n
n
Secondary control variable
n
n
Notes
The smaller this factor the higher the priority to equally share the load among
all generators. If 99 % is configured here, only the primary control reference
variable is considered. If 10 % is configured here, only the secondary control
reference variable is considered.
2
[On]
Reactive power load share is enabled. When multiple generators are oper‐
ating in parallel, the reactive power is shared proportionally.
Off
Reactive power load share is disabled
easYgen-2200/2500 | Genset Control
Isolated operation = frequency maintained
Mains parallel operation = real power level at the mains interchange
point maintained
Isolated operation = real power sharing with other generators maintained
Mains parallel operation = real power sharing with other generators
maintained
Configuration