Woodward easYgen-2000 Series User Manual page 510

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

Appendix
Data Protocols > CANopen/Modbus > Data Protocol 5101 (Basic ...
Modbus
CAN
Modicon
Start
Data
start
addr.
byte 0
addr.
(*1)
(Mux)
450019
450018
6
450020
450019
6
510
Param‐
Description
eter ID
Data
byte
1,2
10202
Operation modes
13200 = Auxiliary services postrun
13216 = Idle run active
13201 = Aux. services prerun
13250 = Gen. stable time
13202 = Critical mode
13251 = In operation
13203 = Motor Stop
13252 = Power limited prerun
13204 = Cool down
13253 = AUTO mode ready
13205 = Mains settling
13254 = Ramp to rated
13206 = Engine Start
13255 = GCB open
13207 = Start – Pause
13256 = Unloading generator
13208 = Preglow
13257 = MCB open
13209 = GCB dead bus close
13258 = Loading generator
13210 = MCB dead bus close
13259 = Synchronization GCB
13211 = Emergency run
13260 = Synchronization MCB
13212 = Turning
13261 = GCB -> MCB Delay
13213 = Ignition
13262 = MCB -> GCB Delay
13214 = Crank protect
13263 = Start w/o Load
13215 = Emergency/Critical
13264 = Unloading mains
13281 = Derating active
13265 = Synchronization permissive
13266 = Synchronization check
13267 = Synchronization off
3,4,5,6
140
Total mains power
easYgen-2200/2500 | Genset Control
Multiplier
Units
(enu
m.)
1
W
37535B