Woodward easYgen-2000 Series User Manual page 94

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

Configuration
Configure Measurement
Dependencies
Fig. 72: AC power triangle
ID
Parameter
235
Generator type
1750
System rated
frequency
94
PF Power Factor
P
Active Power [kW]
S
Apparent power [kVA]
Q
Reactive Power [kvar]
The AC power triangle illustrates the dependencies between active
power, apparent power, reactive power and power factor.
PF = P/S = cos Φ
n
Q = √(S
n
S = √(P
n
P = S * PF
n
CL
Setting range
Description
[Default]
2
The easYgen supports two types of generators:
n
n
[Synchronous]
The unit provides all functions which are needed for synchronous generator
applications. Isolated and mains parallel operation is supported.
Asynchronous
The unit provides the special function of the asynchronousos generator with:
n
n
n
n
n
n
Recommended settings
The asynchronous modus is normally used in mains parallel operation.
Please consider the following settings:
n
n
n
n
n
n
Notes
The asynchron mode is not recommended for emergency power applications.
2
50 / 60 Hz
The rated frequency of the system is used as a reference figure for all fre‐
quency related functions, which use a percentage value, like frequency moni‐
[50 Hz]
toring, breaker operation windows or the Analog Manager.
easYgen-2200/2500 | Genset Control
2
-P
2
)
2
+Q
2
)
synchronous generators
asynchronous generators (induction generators)
The speed is regulated with the speed signal from the MPU or J1939/
CAN input (as long as the GCB is open).
The closing of the GCB is executed, if the speed is within the corre‐
sponding frequency range of the generator operating window. The
voltage and phase angle is ignored in this case.
The generator monitoring (under/over frequency and under/overvoltage)
is switched off, until the generator breaker is closed.
After opening the GCB, under/over frequency and under/overvoltage
monitoring is switched off again.
The Frequency/MPU speed plausibility monitoring is only active, if the
GCB is closed.
The synchroscope is not displayed in the asynchronous modus.
Application mode (parameter
3401 Ä p.
MCB control (parameter
5733 Ä p.
Mains decoupling (parameter
Emergency run (parameter
2802 Ä p.
MPU input (parameter
1600 Ä p.
Generator operating frequency (parameter
5803 Ä p.
108)
200) = GCB/MCB
205) = Off
3110 Ä p.
138) = GCB
245) = Off
242) = On
5802 Ä p.
108,
37535B