Woodward easYgen-2000 Series User Manual page 46

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

Installation
Setup Connections > Voltage Measuring > Generator Voltage
3Ph 4W
Wiring terminals
Terminal
A
14
Phase
L1
3.2.5.1.3
Parameter Setting '3Ph 3W' (3-phase, 3-wire)
Generator windings
Table 7: Generator windings - 3Ph 3W
Measuring inputs
Terminal assignment
3Ph 3W
Wiring terminals
Rated voltage (range)
120 V (50 to 130 V
Measuring range (max.)
0 to 150 Vac
Terminal
A
46
C
E
G
16
18
20
L2
L3
N
For different voltage systems, different wiring terminals
have to be used.
Incorrect measurements are possible, if both voltage
systems use the same N terminal.
Fig. 27: Measuring inputs - 3Ph 3W
)
eff.
C
E
G
easYgen-2200/2500 | Genset Control
B
D
F
15
17
19
L1
L2
L3
480 V (131 to 480 V
)
eff.
0 to 600 Vac
B
D
F
H
21
N
H
37535B