ID
Parameter
5532
Warm up load
limit
5534
Warm up time
5533
Warm up mode
5538
Engine warm
up criterion
5546
Warm up
threshold
37535B
CL
Setting range
Description
[Default]
2
0 to 100 %
The maximum load is limited to this percentage of the generator rated power
(parameter
[15 %]
has expired or the warm up temperature threshold (parameter
5546 Ä p.
2
0 to 9999 s
The maximum load is limited to the value configured in param‐
eter
[0 s]
Notes
This parameter is only effective if Warm up mode (parameter
is configured to "Time controlled".
2
Analog val contr
The maximum load is limited to the value configured in parameter
5532 Ä p. 281
parameter
eter
[Time con‐
The maximum load is limited to the value configured in param‐
trolled]
eter
expired.
2
Determined by
The engine warm up criterion may be selected from the available data
AnalogManager
sources.
Though it is possible to select from all available data sources
Ä Chapter 9.3.1 "Data Sources" on page 533 ), only the following data
(
sources may be used:
[06.01]
Analog input 1
Analog input 1 is used to control the setpoint
06.02
Analog input 2
Analog input 2 is used to control the setpoint
06.03
Analog input 3
Analog input 3 is used to control the setpoint
06.04
Analog input 4
Analog input 4 is used to control the setpoint
Notes
Selecting a different data source may not allow the controller to operate prop‐
erly.
This parameter is only effective if "Warm up mode" (param‐
eter
2
0 to 1000 °C
The maximum load is limited to the value configured in parameter
5532 Ä p. 281
[80 °C]
here.
Notes
This parameter is only effective if Warm up mode (parameter
is configured to "Analog val contr".
easYgen-2200/2500 | Genset Control
Configure Application > Configure Controller > Load Control
1752 Ä p.
95) until the warm up time (parameter
281) has been exceeded.
5532 Ä p. 281
for the time configured here.
until the temperature measured according to the setting in
5538 Ä p. 281
has exceeded the threshold configured in param‐
5546 Ä p.
281.
5532 Ä p. 281
until the time configured in parameter
5533 Ä p.
281) is configured to "Analog val contr".
until the temperature has exceeded the threshold configured
Configuration
5534 Ä p.
281)
5533 Ä p.
281)
5534 Ä p. 281
has
5533 Ä p.
281)
281