Installation
Setup Connections > Voltage Measuring > Generator Voltage
3.2.5.1.1
Parameter Setting '3Ph 4W OD' (3-phase, 4-wire, Open delta)
Generator windings
Table 5: Generator windings - 3Ph 4W OD
Measuring inputs
44
Terminal
Description
A
14
Generator voltage - L1
B
15
C
16
Generator voltage - L2
D
17
E
18
Generator voltage - L3
F
19
G
20
Generator voltage - N
H
21
Table 4: Voltage measuring - generator - terminal assignment
A generator system that is connected to the load through a 3-
phase, 4-wire connection but have the device wired for a 3-phase,
3-wire installation may have the L2 phase grounded on the secon‐
dary side. In this application the device will be configured for 3-
phase, 4-wire OD for correct power measurement.
Fig. 25: Measuring inputs - 3Ph 4W OD
easYgen-2200/2500 | Genset Control
A
max
120 Vac
2.5 mm²
480 Vac
2.5 mm²
120 Vac
2.5 mm²
480 Vac
2.5 mm²
120 Vac
2.5 mm²
480 Vac
2.5 mm²
120 Vac
2.5 mm²
480 Vac
2.5 mm²
37535B