Generator Overload Mop (Level 1 & 2) Ansi# 32 - Woodward easYgen-2000 Series User Manual

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

Configuration
Configure Monitoring > Generator > Generator Overload MOP (Le...
ID
Parameter
2300
Monitoring
2306
2304
Limit
2310
2305
Delay
2311
2301
Alarm class
2307
2302
Self acknowl‐
edge
2308
4.4.1.9
Generator Overload MOP (Level 1 & 2) ANSI# 32
General notes
118
CL
Setting range
Description
[Default]
2
[On]
Overload monitoring is carried out according to the following parameters.
Monitoring is performed at two levels.
Both values may be configured independent from each other (prerequisite:
Level 1 limit < Level 2 limit).
Off
Monitoring is disabled for Level 1 limit and/or Level 2 limit.
2
50.0 to 300.00
The percentage values that are to be monitored for each threshold limit are
%
defined here.
2304: [110.0 %]
If this value is reached or exceeded for at least the delay time without inter‐
ruption, the action specified by the alarm class is initiated.
2310: [120.0 %]
Notes
This value refers to the Generator rated active power (param‐
eter
2
0.02 to 99.99 s
If the monitored generator load exceeds the threshold value for the delay time
configured here, an alarm will be issued.
2305: [11.00 s]
2311: [0.10 s]
Notes
If the monitored generator load falls below the threshold (minus the hyste‐
resis) before the delay expires the time will be reset.
2
Class A/B/C/D/
Each limit may be assigned an independent alarm class that specifies what
E/F
action should be taken when the limit is surpassed.
2301: [B]
2307: [E]
Notes
For additional information refer to
on page 587
2
Yes
The control automatically clears the alarm if the fault condition is no longer
detected.
[No]
The control does not automatically reset the alarm when the fault condition is
no longer detected.
The alarm must be acknowledged and reset by manually pressing the appro‐
priate buttons or by activating the LogicsManager output "External acknowl‐
edgement" (via a discrete input or via an interface).
The power produced by the generator is calculated from the
voltage and current values measured in accordance with how
parameters "Generator voltage measuring" (param‐
eter
1851 Ä p.
eter
1850 Ä p.
easYgen-2200/2500 | Genset Control
1752 Ä p.
95).
Ä Chapter 9.5.1 "Alarm Classes"
MOP = Mains Parallel Operation
96) and "Generator current measuring" (param‐
97) are configured.
37535B