Basic Applications; Application Mode A01 (None) - Woodward easYgen-2000 Series User Manual

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

Application
Basic Applications > Application Mode A01 (None)
6.2

Basic Applications

6.2.1

Application Mode A01 (None)

360
This application mode (
trol is done external. In this case, the easYgen will function as an
engine control with generator and engine protection. The control
does not operate any breaker. Emergency mode (AMF operation)
is not supported in this application mode.
Fig. 138: Application mode A01 (schematic)
The easYgen requires the feedback reply from GCB
and MCB in this application mode. These replies are
used to define, whether the easYgen controls fre‐
quency, shares the load with other gensets or per‐
forms active load control.
The following feedback signals are used in this application mode
and fixed to the respective discrete inputs:
DI 7 "Reply MCB" (mains parallel; normally closed (break) con‐
n
tact)
DI 8 "Reply GCB" (normally closed (break) contact)
n
easYgen-2200/2500 | Genset Control
) may be used, where the breaker con‐
37535B

Advertisement

Table of Contents
loading

Table of Contents