LogicsManager Reference > Factory Settings
Simple (function)
In application mode
,
configurable relay (unassigned)
In application mode
"Command: close
MCB"
Deactivated by default
[00.49] Relay 9 [R09] - Stop solenoid / freely configurable
Relay energizes if the internal condition "Stop
solenoid" is TRUE.
[00.50] Relay 10 [R10] - Auxiliary services / freely configurable
Relay energizes if the internal condition "Aux.
services" is TRUE to activate the auxiliary serv‐
ices (it energizes prior to an engine start and de-
energizes with the engine stop)
[00.51] Relay 11 [R11] - Shutdown alarm / freely configurable
Relay energizes if one of the alarm classes C, D,
E or F is active
[00.xx] External digital output {y} - Free (external expansion card, if connected; {xx} = 63 to 78 ; {y} = 1 to 16)
Control of the external relay {y}, if this is con‐
nected
Prepared for:
Deactivated by default
586
Extended (configuration)
, and
= freely
easYgen-2200/2500 | Genset Control
Result
FALSE
dependent on
application
mode and
Logics Com‐
mand Variable
[03.27]
dependent on
Logics Com‐
mand Variable
[03.01]
dependent on
Logics Com‐
mand Variable
[01.09]
FALSE