Woodward easYgen-2000 Series User Manual page 579

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

Simple (function)
[00.12] Undelay close GCB
If TRUE, the GCB will be closed in an emer‐
gency operation without waiting for expiration of
the delayed engine monitoring.
TRUE once emergency mode is enabled.
Only available in application mode
operating modes "AUTO" and "MAN".
[00.14] Constant Idle run
If TRUE, the control outputs an "Constant idle
run" if a start request for the generator is present
Deactivated by default.
[00.15] External acknowledgment
If TRUE, all alarms are acknowledged from an
external source.
TRUE once discrete input [DI 05] is energized.
[00.16] Operation mode AUTOMATIC
If TRUE the unit changes into AUTOMATIC
operating mode.
Deactivated by default.
[00.17] Operation mode MANUAL
If TRUE the unit changes into MANUAL oper‐
ating mode.
Deactivated by default.
[00.18] Operation mode STOP
37535B
Extended (configuration)
,
and
easYgen-2200/2500 | Genset Control
LogicsManager Reference > Factory Settings
Appendix
Result
dependent on
emergency
operation
FALSE
dependent on
discrete input
[DI 05]
FALSE
FALSE
579