Woodward easYgen-2000 Series User Manual page 291

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

ID
Parameter
5614
Integral gain
5615
Derivative ratio
5660
Deadband
5661
Time pulse
minimum
37535B
Configure Application > Configure Controller > Power Factor Control
CL
Setting range
Description
[Default]
2
0.01 to 100.00
The integral gain identifies the I part of the PID controller. The integral gain
corrects for any offset (between setpoint and process variable) automatically
[1.00]
over time by shifting the proportioning band.
Reset automatically changes the output requirements until the process vari‐
able and the setpoint are the same. This parameter permits the user to adjust
how quickly the reset attempts to correct for any offset. The integral gain con‐
stant must be greater than the derivative time constant.
If the integral gain constant is too large, the engine will continually oscillate. If
the integral gain constant is too small, the engine will take too long to settle at
a steady state.
Notes
This parameter is only visible if power factor control (param‐
eter
2
0.01 to 100.00
The derivative ratio identifies the D part of the PID controller. By increasing
this parameter, the stability of the system is increased.
[0.01]
The controller will attempt to slow down the action of the actuator in an
attempt to prevent excessive overshoot or undershoot.
Essentially this is the brake for the process. This portion of the PID loop oper‐
ates anywhere within the range of the process unlike reset.
Notes
This parameter is only visible if power factor control (param‐
eter
The default configured controller acts like a PI controller what is the valid D
part setting for systems with secondary controllers.
1
0.001 to 0.300
The generator power factor is controlled in such a manner, when paralleled
with the mains, so that the monitored power factor does not deviate from the
[0.010 %]
configured power factor setpoint by more than the value configured in this
parameter without the controller issuing a raise/lower signal to the voltage
regulator.
This prevents unneeded wear on the raise/lower relay contacts.
Notes
This parameter is only visible if power factor control (param‐
eter
1
0.01 to 2.00 s
A minimum pulse on time must be configured here.
[0.05 s]
The shortest possible pulse time should be configured to limit overshoot of
the desired power factor reference point.
Notes
This parameter is only visible if power factor control (parameter
5625 Ä p.
easYgen-2200/2500 | Genset Control
5625 Ä p.
290) is configured to "PID analog".
5625 Ä p.
290) is configured to "PID analog".
5625 Ä p.
290) is configured to "3pos controller".
290) is configured to "3pos controller".
Configuration
291