Woodward easYgen-2000 Series User Manual page 96

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

Configuration
Configure Measurement
ID
Parameter
1859
1Ph2W phase
rotation
1851
Generator
voltage meas‐
uring
96
CL
Setting range
Description
[Default]
Notes
For information on measuring principles refer to
Voltage" on page 43 .
Never configure the busbar measurement for phase-neutral, if the other sys‐
tems like mains and generator are configured as 3Ph 3W or 3Ph 4W. The
phase angle for synchronization would be not correct.
3
[CW]
A clockwise rotation field is considered for 1Ph 2W measuring .
CCW
A counter-clockwise rotation field is considered for 1Ph 2W measuring.
Notes
For information on measuring principles refer to
Voltage" on page 43 .
2
3Ph 4W OD
Measurement is performed Line-Neutral (Open Delta connected system). The
voltage is connected via transformer with 3 Wire.
Phase voltages and the neutral must be connected for proper calculation.
Measurement, display and protection are adjusted according to the rules for
Open Delta connected systems.
Monitoring refers to the following voltages:
n
[3Ph 4W]
Measurement is performed Line-Neutral (WYE connected system) and Line-
Line (Delta connected system). The protection depends on the setting of
parameter
Phase voltages and the neutral must be connected for proper calculation.
Measurement, display and protection are adjusted according to the rules for
WYE connected systems.
Monitoring refers to the following voltages:
n
n
3Ph 3W
Measurement is performed Line-Line (Delta connected system). Phase vol‐
tages must be connected for proper calculation.
Measurement, display and protection are adjusted according to the rules for
Delta connected systems.
Monitoring refers to the following voltages:
n
1Ph 2W
Measurement is performed Line-Neutral (WYE connected system) if param‐
eter
nected system) if parameter
Measurement, display and protection are adjusted according to the rules for
phase-phase systems.
Monitoring refers to the following voltages:
n
easYgen-2200/2500 | Genset Control
VL12, VL23 and VL31
1770 Ä p.
107.
VL12, VL23 and VL31 (parameter
phase")
VL1N, VL2N and VL3N (parameter
neutral")
VL12, VL23, VL31
1858 Ä p. 95
is configured to "Phase - neutral" and Line-Line (Delta con‐
1858 Ä p. 95
VL1N, VL12
Ä Chapter 3.2.5.1 "Generator
Ä Chapter 3.2.5.1 "Generator
1770 Ä p. 107
configured to "Phase-
1770 Ä p. 107
configured to "Phase-
is configured to "Phase - phase".
37535B