Multi-Unit Missing Members - Woodward easYgen-2000 Series User Manual

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

ID
Parameter
4070
Monitoring
4071
Alarm class
4.4.6.11

Multi-Unit Missing Members

General notes
ID
Parameter
4061
Alarm class
37535B
Configure Monitoring > Miscellaneous > Multi-Unit Missing Members
CL
Setting range
Description
[Default]
2
[On]
Multi-unit parameter alignment monitoring is carried out.
Off
Monitoring is disabled.
2
Alarm class
This function may be assigned an independent alarm class that specifies
Class A/B/C/D/
what action should be taken when this function triggers an alarm.
E/F
[B]
Notes
For additional information refer to
on page 587 .
The multi-unit missing members monitoring function checks
whether all participating units are available (sending data on the
load share line).
If the number of available units is less than the number of mem‐
bers configured in parameter
time, the display indicates "Missing members" and the logical com‐
mand variable "08.17" will be enabled.
CL
Setting range
Description
[Default]
2
Class A/B/C/D/
This function may be assigned an independent alarm class that specifies
E/F
what action should be taken when this function triggers an alarm.
[B]
Notes
For additional information refer to
on page 587 .
easYgen-2200/2500 | Genset Control
Ä Chapter 9.5.1 "Alarm Classes"
4063 Ä p. 190
After energizing the easYgen, a delay is started, which
allows a possible "Missing members" alarm to become
active. This delay depends on the Node-ID of the
easYgen (parameter
8950 Ä p.
rate of a load share fast message (param‐
eter
9921 Ä p.
322) and may last for approx. 140 sec‐
onds for a high Node-ID (e.g. 127). This delay serves
for detecting the Master of a CAN bus connection.
Approximately two minutes after energizing the
easYgen, the alarm delay will be set to a fix time,
which depends on the setting of param‐
eter
9921 Ä p. 322
(Transfer rate LS fast message)
and is in the range between 3 to 12 seconds.
Ä Chapter 9.5.1 "Alarm Classes"
Configuration
for at least the delay
309) and the transfer
189