Configuration
Function Of Inputs And Outpu... > Discrete Inputs
Input
Type/Preset
Discrete input [DI 01]
Programmable
Preconfigured to "Emergency stop"
Discrete input [DI 02]
Programmable
Preconfigured to "Start in AUTO"
Discrete input [DI 03]
Programmable
Preconfigured to "Low oil pressure"
Discrete input [DI 04]
Programmable
Preconfigured to "Coolant temperature"
Discrete input [DI 05]
Programmable
Preconfigured to "Alarm acknowledge"
Discrete input [DI 06]
Programmable
Preconfigured to "Enable MCB"
102
Programmable
n
The discrete input has been assigned a default function
using either the LogicsManager or preconfigured alarms
such as "emergency stop".
The following sections describe how these functions are
assigned.
The function of a discrete input can be changed if required.
The following description of the inputs, labeled with "pro‐
grammable", refers to the preconfiguration.
Fixed
n
The discrete input has a specific function that cannot be
changed depending upon the configured application mode.
Description
This discrete input is configured as alarm class F and is not
delayed by the engine speed.
Enabled in the AUTOMATIC operation mode
This discrete input is configured as a Control input in the alarm
class and is not delayed by the engine speed.
n
n
This discrete input is configured as alarm class B and is
delayed by the engine speed.
This discrete input is configured as alarm class B and is not
delayed by the engine speed.
This discrete input is used as a remote acknowledgement for
alarms. The input is normally de-energized. When an alarm is
to be acknowledged the input is energized. The first time an
alarm in acknowledged, the centralized alarm/horn is silenced.
When the input is energized a second time, all alarms, which
are no longer active, will be acknowledged.
This discrete input is configured as a Control input in the alarm
class and is not delayed by the engine speed.
Only applicable for application mode
This discrete input is configured as a Control input in the alarm
class and is not delayed by the engine speed.
n
n
easYgen-2200/2500 | Genset Control
Energized
If the unit is in the AUTOMATIC operation mode (selected
with the operating mode selection push button on the front
panel) the controlled engine is started automatically.
De-energized
The engine is stopped.
Energized
The MCB is enabled and closure of the breaker is per‐
mitted.
De-energized
The MCB is not enabled and closure of the breaker is not
permitted. This function permits a supervisory control (i.e.
a PLC) to allow the closure of the MCB by the easYgen.
37535B